Mar 07, 2022 Ħalli messaġġ

How to solve the common faults of the TRG meter of the Dalian TEIKOKU canned pump?

How to solve the common faults of the TRG meter of the Dalian TEIKOKU canned pump?

The principle of canned pump TRG meter:

IMG_0963_

One coil is buried above and below the stator coil of the shielded pump (which can be understood as the top and bottom of a horizontally placed cylinder), and the two coils are connected, but the phases are opposite, such as "the center line of the rotor" and "the geometric center line of the two coils {{0}} pump If the center line of the bearing is coincident, then the upper and lower coils induce voltages of equal magnitude but opposite phases, which cancel each other out, and the current is 0, which means that the TRG meter is at 0, which is the lowest point of the green zone. When the bearing is worn, the rotor center line At this time, the induced currents of the upper and lower coils are not equal in magnitude. After a certain treatment, the current is generated, and the TRG pointer also changes with the magnitude of the current. However, such as in the green area, the rotor offset caused by the bearing wear is acceptable. , the rotating rotor will not wear the shielding sleeve and can continue to run, but when the pointer is in the yellow zone, it means that the wear is increasing, and the bearing must be repaired and replaced. After the red zone, it indicates that the rotor has worn the shielding sleeve, and it must be disassembled at this time. Check whether the shielding sleeve is in good condition. If it is worn, please return it to the factory for repair. The watch plays a very important role in the daily maintenance of the shielded pump.

It can be seen from the above that the TRG meter only detects the radial wear of the bearing, because after the radial wear, the rotor centerline can be offset, and the axis offset of the rotor cannot be detected by this meter, but if the axial offset is too large, it will cause a certain pump. The wear of the place will cause the current to be too high. If there is a current protection device, it will trip, but it will not cause damage to the pump. Generally, it can be solved by replacing the thrust plate and bearing.

To sum up: TRG meter and ammeter are the windows to confirm whether the canned pump is running well.

TRG instructions

No.

TRG indication and electric pump status

Possible fault point

Check or treatment method

1

The hands of the watch gradually   increase, the pointer does not swing, and sometimes the operation is not good

The power supply voltage increases or the   bearing wear increases.

First check whether the terminal voltage   is normal, and then check the bearing wear. If it exceeds the value, replace   the bearing with a new one.

2

The needle swings irregularly, the flow   and pressure of the electric pump are unstable, the internal sound is   abnormal, and sometimes the end is heated

The circulating fluid system is abnormal,   the flow is insufficient or there is air

Check the circulating fluid pipeline and   check whether the type of electric pump meets the process requirements

3

The hands suddenly rise to the red zone,   and the swing of the hands increases and fluctuates regularly. Sometimes   restart after shutdown, the fault disappears

The expansion of the rotor cage bars   causes local breakage

Replace with a new rotor of the same   model

4

The needle suddenly rises to the red   area, the swing of the needle increases and there are regular.fluctuations   accompanied by abnormal sound inside the pump

The impeller shakes, the rotating shaft   is bent, and the mouth ring is worn

Disassemble the electric pump casing to   check and repair the damage

5

The needle is greater than 0.75, the   operation sound is not smooth, and the flow and pressure are low

Phase sequence reversed

Check power phase sequence and reconnect   power

6

The needle is normal, the operation is   not smooth, the flow pressure is low or the operation is normal, and the   needle is greater than 0.75

The three-phase power supply of the   module does not match the phase sequence of the motor terminals. TRG and   thermal element circuit are reversed

Check the phase sequence of the   three-phase power supply of the module and the lead wires of the motor   terminals and connect them in the correct phase sequence

7

The needle is normal, the operation is   not smooth, the flow pressure is low or the operation is normal The needle is   greater than 0.75

The three-phase power supply of the   module does not match the phase sequence of the motor terminals. TRG and   thermal element circuit are reversed

Check the phase sequence of the   three-phase power supply of the module and the lead wires of the motor   terminals and connect them in the correct phase sequence

8

When the needle is greater than 0.5, the   current of one phase is zero

out of phase

Check the power cord and connect the   power

9

The hands of the watch are suddenly large   and small or swing, this phenomenon is temporary

The pipeline is mixed with foreign   matter, or the working fluid has crystals or precipitates

Check the working fluid and circulation   pipeline, and discharge foreign matter

10

The electric pump works normally, the   positive and reverse connection of the power cord is always greater than   0.75, and sometimes the fault disappears after stopping for one stage and   then restarting

The module or TRG meter is damaged or the   TRG system loop is grounded

Check the input and output electrical   parameters of the module, check the grounding points of the modules, circuit   boards and electrical circuits

11

hands do not indicate or reverse

The polarity is reversed when the module   is reassembled after inspection. The instrument is damaged and the module is   selected incorrectly

Check the selection type of the instrument   and the module, whether the module mounting hole and the polarity of the   instrument conform to

12

Table does not move in a certain position

Card pin

Remove the meter to check

13

The main circuit terminal has zero   insulation to ground, or trips when starting the electric pump

The wiring frame is damaged, the module   is damaged, and the main winding is damaged. TRG and thermal element circuit   are reversed

Remove the module and main winding from   the wiring frame and check separately


Production Application

 

The company's main business scope includes: central air-conditioning maintenance, cleaning and technical services; cooling tower and fan coil cleaning and maintenance services; custom processing of lithium bromide solution; sales of lithium bromide solution special impurity separators; central air-conditioning host and various zero Sales of accessories; installation and sales of central air conditioning systems, etc.

Widely used in major air-conditioning systems and process refrigeration cold and heat sources; in steel, textile, chemical, electronics, pharmaceutical, food and other industrial and mining enterprises, as well as hotels, theaters, hospitals, and large commercial buildings , Central heating stations and other occasions are widely used.

 

Contact Us

 

Ms. Guo- Sales Support Operations Manager.

 

Email: mdguolijuan@zjflier.com

 

Mob: plus 8615358588768

 

WeChat: 8615358588768

 

WhatsApp: 15358588768

 

 

 


Ibgħat l-inkjesta

whatsapp

Tat-telefon

Indirizz elettroniku

Inkjesta